Description
Online Rack
The Online Rack Series with microprocessor and
True Double Conversion, guarantees a signal
stable and clean to all connected equipment.
Allows the installation of battery banks
external in all its references, and has
protected RJ45 sockets, which will offer protection
against over-voltages and electrical noise for your
Telephone / ADSL / Ethernet connection
Specs
-
Power 2000VA / 1800W
- Entrance
- Transfer voltage - Low 160 VAC/140 VAC/120 VAC/110 VAC±
- Return Voltage - Low 170 VAC/150 VAC/130 VAC/120 VAC ± 5 %
- Transfer voltage - High 150 VAC ± 5% or 300 VAC ± 5%
- Return Voltage - High 145 VAC ± 5% or 290 VAC ± 5%
- Frequency Range 45Hz~55Hz or 56Hz~65Hz
- Phase Monophase + neutral
- Power factor ≧ 0.99 @ 200-230 VAC or 100-120 VAC
- Exit
- Output voltage 200/208/220/230/240 VAC
- AC voltage regulation ± 1%
- Frequency Range Sync /
- Bat 48~52 Hz 58~624 Hz / 50 Hz ± 0.2 Hz or 60 Hz ± 0.3 Hz
- Peak current value 3:1 (max.)
- Harmonic distortion ≦ 2 % THD (linear load) / ≦ 8 % THD (non-linear load)
- AC/Battery overload protection
- 100%~110%: 10 min. 110%~130%: 1min. >130%: 1 sec /
- 100%~110%: 30 sec. 110%~130%: 10 sec. >130%: 1 sec
- Transfer Time. (AC / BYPASS) 0 ms / 4 ms (Typical)
- Waveform (Bat.) Pure Sinusoidal
- AC/Battery Efficiency 90% / 89% 91% / 89%
- Battery
- Quantity / Type / No. 4x 12V / 9Ah
- Charging time (90%) 4h
- Charging Current/Voltage
- 1.0 A (Max.) / 54.8 VDC ± 1%
- Characteristics
- Dimensions (DxWxH) 510 x 438 x 88 (2U)
- Weight (Kg) 19.5
- Operating Humidity 20 - 90% non-condensing @ 40º C
- Noise level < 50dBA @ 1 meter